Liebert AC Power Low Exposure Transient Voltage Surge Suppressor, electronic grade surge
protective device designed with sine wave tracking to protect electronic equipment and
microprocessor-based systems from transients on distribution panels, branch panels, or equipment in
low exposure locations. Dry contacts for remote indication standard.
AC Power Low Exposure TVSS Technical Specification
Connection Type................................................. Parallel
Operating Voltage Range................................... +/-15%
Fault Current Rating (AIC).................................. 14 kAIC
Dimensions ..................... .................................... 4.72”x4.72”x2.36”
Operating Frequency Range ............................. 47 – 63 Hz
Capacity................................................................ Continuous
50 EMI/RFI Attenuation................................... 40 dB
Response Time.................................................... <0.5 ns
Dry Contract rating.............................................. 125vac, 8.0A, 1.0pf
Operating Temperature ...................................... -40ºc to +50ºc
Operating Humidity............................................. 0% to 95%
Status Indication.................................................. LED, Dry Contacts
Certifications........................................................ UL 1449, CUL, CE, ISO 9001
Warranty ............................................................... 5 Years
UL 1449 (second edition) Classification
120 volt systems.................................400 volts all modes
208 through 277 volt systems ..........800 volts all modes
480 volt systems.................................1,500 volts all modes
ORDERING INFORMATION
Building A Model Number: LPL 1 2 3
1: Nominal Voltage Requirements
Nominal Voltage Requirements Model ID
L-N L-L L-G
2: System Configuration
3: Surge Current Capacity
System Configuration
Model ID
120 ........N/A....... 120
120 .......208 ...... 120
120 ........240....... 120
N/A ........208....... 208
230 ........400....... 230
N/A ........240....... 240
277 ........480....... 277
N/A ........400....... 400
N/A ........480....... 480
120
120
120
208
230
240
277
400
480
Single (2 Wire + Gnd)
Split (3 Wire + Gnd)
Wye (4 Wire + Gnd)
Delta Hi-Leg (4 Wire + Gnd)
Delta (3 Wire + Gnd)
N or L
S
Y
H
D
PANEL I.D.
MODEL NUMBER(S)
Surge Current Capacity
Model ID
100
100 kA/Phase
(L-N: 50 kA + L-G: 50 kA; N-G: 50 kA)
50 kA/Phase 50
(L-N: 25 kA + L-G: 25 kA; N-G: 25 kA)
25 kA/Phase
25 – 2
(L-N: 25 kA; N-G: 25 kA)
Job Name _______________________
Model #_________________________
Date ___________________________
Qty ____________________________
Quote #_________________________
Liebert Corporation • 1050 Dearborn Drive • PO Box 29186 • Columbus, OH 43229
Phone 607-724-2484 • Fax 607-722-8713 • US & Canada 800-288-6169
82247 Rev 0
|
Land Pride Brush Cutter RC25 User Manual
Life Fitness Elliptical Trainer 14 90 Series User Manual
Life Fitness Exercise Bike M051 0K66 A149 User Manual
Life Fitness Home Gym G3 User Manual
Mackie Musical Instrument HMX 56 User Manual
Magnadyne Car Video System MV 1002 User Manual
Marantz Stereo Amplifier PM7001KI User Manual
Maytag Washer W10270227 User Manual
Melissa Styling Iron 635 094 User Manual
MGE UPS Systems Power Supply Comet TM 5 30 kVA User Manual